EATON

Circuit Breaker, Engine Generator; 600V AC; 3P

(9 Product Options) Manufacturer Series: FG
  • Type: Engine Generator Breaker
  • Trip: Standard Thermal, Fixed Magnetic
  • Voltage Max: 600V AC
  • Poles: 3P
View All Specifications

Filters

Filter Table By

Loading...

Applied Filters

Clear Filters
Part #    
 
-
-
Type: Engine Generator Breaker
Trip: Standard Thermal, Fixed Magnetic
Voltage Max: 600V AC
Poles: 3P
Magnetic Pickup Range: Fixed
Dimensions: 5 x 7 x 5 in. (127 x 178 x 127mm)
Options: Shunt Trip 12-24V AC/DC Left Pigtail Opposite Side

Eaton engine generator molded case circuit breakers are designed specifically for application on diesel engine powered standby generators where high interrupting circuit breakers are not required. Special low magnetic pickup range. The standard thermal trip unit provides overload protection for conductors per the national electrical code. The low magnetic pickup range is approximately two to five times the continuous rating and provides closer low level short circuit protection when applied on generators that have very low short circuit capacity. This combination allows the user to customize the breaker to the generator output.